Analysis of Summer Heating Load for Conference-Hall of NIT Raipur |
Author(s): |
| Amit Dubey , ICFAI University Raipur |
Keywords: |
| Cooling load, conduction, ventilation, heat gain, air-conditioner |
Abstract |
|
This paper represents analytical approach of calculation of cooling load and air-conditioner required for the conference hall of National Institute of Technology (NIT) Raipur. The city Raipur (Latitude: 20.92N, Longitude: 82.00E) is the capital of state Chhattisgarh of India. The climatic condition of Raipur comes under composite zone of climate classification of India, where the summer is quite hot and temperature ranges 42̊C-45̊C in the month of May. The total heat load of conference hall and the required number of air conditioner of 1.5 ton capacity has been calculated by considering conduction heat gain, ventilation heat gain, solar heat gain and internal gain. For the taken dimensions and structural properties of the conference hall the cooling load of the hall is 42.5 kw and the required number of air conditioner is 8. |
Other Details |
|
Paper ID: IJSRDV2I9459 Published in: Volume : 2, Issue : 9 Publication Date: 01/12/2014 Page(s): 627-629 |