Comparison of Shunt Facts Devices for the Improvement of Transient Stability of Two Machine Power System Using MATLAB Modelling

Author(s):

Arti Devi Patel , JABALPUR ENGINEERING COLLEGE JABALPUR

Keywords:

Transient stability; FACTS devices; SVC, STATCOM; MATLAB/SIMULINK

Abstract

This paper presents, the performance of STATCOM placed at midpoint of the two machine power system and compared with the performance of SVC. The comparison of various results found for the different type of faults (single line, double line & three phase fault) occur in long transmission line, and their removal by using shunt FACTS devices is analysed. Computer simulation results under a severe disturbance condition (three phase fault) for different fault clearing times, and different line lengths are analyzed. Both controllers are implemented using MATLAB/SIMULINK. Simulation results shows that the STATCOM with conventional PI controller installed with two machine three bus systems provides better damping oscillation characteristics in rotor angle as compared to two machine power system installed with SVC. The transient stability of two machine system installed with STATCOM has been improved considerably and post settling time of the system after facing disturbance is also improved.

Other Details

Paper ID: IJSRDV3I100760
Published in: Volume : 3, Issue : 10
Publication Date: 01/01/2016
Page(s): 944-948