High Impact Factor : 4.396 icon | Submit Manuscript Online icon |

Performance Analysis of Axial Flow Cooling Coil and Mixed Flow Cooling Coil in a Cold Storage using Numerical Method

Author(s):

Rajkumar Bhadu , Maulana Azad National institute Of Technology Bhopal; Dr. K.R. Aharwal, Maulana Azad National institute Of Technology Bhopal; Abhinav Rajan, Maulana Azad National institute Of Technology Bhopal

Keywords:

Axial Flow Arrangement, Mix Flow Arrangement, CFD, Air Temperature, Average Temperature Of Cold Chamber, Bins, Cold Storage

Abstract

In cold storage maintaining preservation temperature uniformly for preserving food is difficult to attain. This paper represents the temperature distribution and velocity distribution for axial flow evaporator and mix flow evaporator arrangement in a refrigerated cold storage. The cooling chamber under analysis has an axial flow cooling coil arrangement located at top of the wall and mix flow cooling coil (discharge through centre and circumferential) located at centre of roof in front of column of bins. A CFD analysis is done under steady state for air flow distribution and temperature distribution using a three dimensional model. In this paper a three dimensional model for a cold storage [10 m(l)× 8 m(w)×9m(h)] prepared. The performance analysis done for both the coils arrangement having the same cooling capacity, air velocity and discharge temperature. It is found that during mix flow arrangement the average temperature of cold chamber and cooling effectiveness was lower than the axial flow cooling coil arrangement.

Other Details

Paper ID: IJSRDV3I40725
Published in: Volume : 3, Issue : 4
Publication Date: 01/07/2015
Page(s): 3004-3009

Article Preview

Download Article