High Impact Factor : 4.396 icon | Submit Manuscript Online icon |

Impact of Varying Height to Diameter Ratio of Intze Tank on Different Component of Tank

Author(s):

Virendra Sahu , SRK University, Bhopal, India ; Satish Kumar Prabhakar, SRK University, Bhopal, India ; Dr. Pankaj Singh, SRK University, Bhopal, India

Keywords:

Intze Tank, Water Storage Tank

Abstract

Intze tank is an important overhead water storage tank, there for it is necessary that it should be constructed keeping in view its economy. To obtain economical design of tank, the proportion of container such as, staging container diameter ratio, height of cylindrical wall container diameter ratio and horizontal angle of dome have been varied as well as no of column for design of staging .To achieve this objective 15 different depth to diameter ratio of Intze tank. For this purpose a computer program in Microsoft excel has been developed. In Microsoft excel program continuity correction have been work out .The design of container is carried out by working stress method but staging is carried out by using limit state method. To get the economical design of Intze tank horizontal angle of conical dome should be 'less than 45°, ratio of height of cylindrical wall and container diameter ratio should be between 0.3 and 0.35.0n the other hand staging container diameter ratio effects the economy of higher capacity of tank only.

Other Details

Paper ID: IJSRDV6I100327
Published in: Volume : 6, Issue : 10
Publication Date: 01/01/2019
Page(s): 522-526

Article Preview

Download Article