Design of Heating Ventilation Air Conditioning With Variable Refrigerant Flow System for two Storey Educational Building of IET DAVV Indore |
Author(s): |
| Mukesh Waskel , MJP GOVT .POLYTECHNIC COLLEGE KHANDWA; Dr. Sharad Chaudhary, IET DAVV INDORE |
Keywords: |
| HVAC, TR, A/C System, HP |
Abstract |
|
In this paper design of HVAC system in favor of VRF system, the main reason for that high energy saving and low cost if the load of building below 90 TR as per market survey of various HVAC systems. There is calculating the size of HVAC system according to estimated the cooling load of two storey's educational building of IET DAVV located at Indore city on June month. Through the calculation it is obtained that total heat gain in the ground floor is about (20.71 TR) and first floor is about (41.53TR) for that load we have proposed the size of the VRF system. For ground floor and first floor indoor units are (cassettes, ductable and Hi- wall) about 27.84 TR and 60.93 TR. Outdoor unit for ground floor and first floor are about 16 HP and 44 HP, included ventilation load by pass factor and factor of safety and diversity. |
Other Details |
|
Paper ID: IJSRDV6I10964 Published in: Volume : 6, Issue : 1 Publication Date: 01/04/2018 Page(s): 1429-1432 |